King Edward Commercial Centre: solar, battery and EV charging stations
- The King Edward Commercial Centre at 488 King Edward Rd, Osborne Park WA 6017 (view on Google Maps) will be configured as a micro-grid incorporating a rooftop solar array, a battery and EV chargers set against the centre’s existing site load including existing tenancies, a showroom with air-conditioning and a small data centre. The battery will be registered for the Western Australia Reserve Capacity Mechanism and provide grid support between the peak hours of 16:00 and 21:30 discharging 1 MW per hour over seven hours.
- The battery needs to be full at 06:00. It must be full again at 16:00, when it starts discharging to the grid for seven hours. Overnight it recharges from the grid, limited by the connection, ready for 06:00. The HVO genset size is 500 kW. The sliders dictate how long and when the HVO genset needs to be operational in order to have the battery fully charged at 06:00 and again at 16:00 for the Reserve Capacity Mechanism scheme.
- The centre’s existing site load, from its historic energy use for July 2024 to June 2025, averages 534 kWh a day (22.2 kW) across the year. The seasonal averages below are for each day of the season; summer is December to February, autumn March to May, winter June to August and spring September to November.
- Summer: 633 kWh a day, an average of 26.4 kW, with 67% of the energy in the on-peak period.
- Autumn: 538 kWh a day, an average of 22.4 kW, with 63% on-peak.
- Winter: 534 kWh a day, an average of 22.2 kW, with 61% on-peak.
- Spring: 431 kWh a day, an average of 17.9 kW, with 65% on-peak.
- The data centre is a forecast addition, not a metered load: 28.6 kW for 22 hours a day, about 629 kWh a day and 229,429 kWh a year, taken as the same in every season. The showroom air-conditioning is also a forecast addition, and varies with the season from 20% to 90% of its full draw.
- See the Show the numbers section below for more detailed information on power consumption and loads.
*7 MWh is the usable energy in the battery. A battery with 7 MWh usable needs to be sized at at least 8.5 MWh.
The EV Chargers use the cluster rating, multiplied by the time in use, for the 17 hours from 06:00 to 23:00: .
Battery energy
- With top-up
- Without top-up
- Held for RCM and grid support
- Overnight recharge
Power in and out
- Centre load, including EV Chargers
- Solar Array
- Top-up
- Grid import, overnight
- Grid import limit
The centre’s own load runs all day. From 06:00 to 16:00 the battery and the solar array supply it. After 16:00 its load comes from grid import, solar and the genset, or from the battery if you choose that above. Overnight the grid import limit is shared between the centre’s load and the battery recharge.
Load and solar, month by month
- Existing load
- Showroom air-conditioning
- Data centre
- EV Chargers
- Solar Array
Where the green line is above the stack the array makes more than the centre uses in that month. The genset is needed most in the months when the array makes least, because the battery is drawn down to supply the centre from 06:00.
Show the numbers
Model: one-minute steps from 06:00 to 06:00 the next morning, for an average day: the average of the whole year, or of the month you choose. The year runs one such day for each month and multiplies by the days in the month. The battery starts the day full. From 06:00 to 16:00 the solar array and the battery supply the centre’s load; if the battery is below full at 16:00 the top-up starts as late as possible so that it is full at 16:00. The top-up delivers 95% of its rated power to the battery. From 16:00 to 23:00 the battery discharges to the grid at the dispatch rate. The overnight recharge starts at 23:00 and delivers 95% of the grid power that is left after the centre’s load, up to the import limit. If the battery would still be short at 06:00, the genset also runs before 06:00, starting as late as possible so that the battery is full at 06:00, and adds 95% of its rated power to the battery on top of the grid import. The EV Chargers run from 06:00 to 23:00. Battery losses are otherwise ignored.
Existing load is the centre’s historic on-peak and off-peak energy for July 2024 to June 2025, spread evenly over 08:00 to 22:00 (on-peak, assumed) and the other ten hours. Showroom air-conditioning is forecast at 45.2 kW for 10 hours a day (assumed 08:00 to 18:00), at a monthly share of 20% to 90% of full draw. The data centre is forecast at 28.6 kW for 22 hours a day (assumed 00:00 to 22:00). Both are from a 2025 forecast prepared for the centre; the EV Chargers in that forecast were 500 kWh a day, and are the least certain of the loads. Solar is the forecast monthly yield for a 500 kW array, scaled to the array you choose and shaped as a half-sine from 06:00 to 18:00. Weekdays and weekends are not separated, and cloud and tariffs are not modelled. These are illustrative figures, not a design.
*7 MWh is the usable energy in the battery. A battery with 7 MWh usable needs to be sized at at least 8.5 MWh.